K-FLEX rubber foam insulation is suitable for all applications both civil and industrial that require the use of insulation material, without neglecting the price/quality relationship: refrigeration, air-conditioning, heating and plumbing, tanks, pipe fittings and water ducts.
Insulation tubes – length 2m | |
Thickness | Diameter |
6 - 9 - 13 - 19 - 25 - 32 - 40 - 50 - 55 - 60 mm | from 06 to 168 mm |
Temperature range | +110 °C | |
Fire Class | Euroclass B, S3, d0 EN 13501-1, Cl. 1 (I), M1 (E), BS 476 PT 7 CL 1 (UK) | |
Thermal conductivity λ W/(m•K) EN 12667 (DIN 52612) ENISO 8497 (DIN 52613) |
Thickness < 25mm -20 °C = 0,031 0 °C = 0,033 +20 °C = 0,035 +40 °C = 0,037 |
Thickness > 25mm -20 °C = 0,034 0 °C = 0,036 +20 °C = 0,038 +40 °C = 0,040 |
Permeability µ EN12086 (DIN 52615) |
µ >7000 | |
Corrosion problems | EN 13468; pH неутрално (7±1) |
Tubes 2092 x 387 х 322 mm |
![]() |